BASIC INFO
						
					
					
	Pepperl+Fuchs KCD2-STC-Ex1 Transmitter Power Supply Isolated Barrier
	Features
	• 1-channel isolated barrier
	• 24 V DC supply (Power Rail)
	• Input for 2-wire SMART transmitters and current sources
	• Output for 4 mA ... 20 mA or 1 V ... 5 V
	• Sink or source mode
	• Housing width 12.5 mm
	• Up to SIL 2 acc. to IEC 61508
	
	 
	Function
	This isolated barrier is used for intrinsic safety applications.
	The device supplies 2-wire SMART transmitters in a
	hazardous area, and can also be used with 2-wire SMART
	current sources.
	It transfers the analog input signal to the safe area as an
	isolated current value.
	Digital signals may be superimposed on the input signal in the
	hazardous or safe area and are transferred bi-directionally.
	Selectable output of current source, sink mode, or voltage
	output is available via DIP switches.
	If the HART communication resistance in the loop is too low,
	the internal resistance of 250 Ω between terminals 6 and 8
	can be used.
	Test sockets for the connection of HART communicators are
	integrated into the terminals of the device.
	Application
	The device supports the following SMART protocols:
	• HART
	• BRAIN
	
	
	
		 
	
		General specifications
		 
	
		Signal type Analog input
	
		Functional safety related parameters
	
		Safety Integrity Level (SIL) SIL 2
	
		Supply
	
		Connection Power Rail or terminals 9+, 10-
	
		Rated voltage Ur 19 ... 30 V DC
	
		Ripple ≤ 10 %
	
		Rated current Ir ≤ 45 mA
	
		Power dissipation ≤ 800 mW
	
		Power consumption ≤ 1.1 W
	
		Input
	
		Connection side field side
	
		Connection terminals 1+, 2-; 3+, 4-
	
		Input signal 4 ... 20 mA limited to approx. 30 mA
	
		Open circuit voltage/short-circuit current terminals 1+, 2-: 22 V / 30 mA
	
		Voltage drop terminals 3+, 4- : approx. 5 V
	
		Available voltage terminals 1+, 2-: ≥ 15 V at 20 mA
	
		Output
	
		Connection side control side
	
		Connection terminals 5-, 6+
	
		Load 0 ... 300 Ω (source mode)
	
		Output signal 4 ... 20 mA or 1 ... 5 V (on 250 Ω, 0.1 % internal shunt)
	
		4 ... 20 mA (sink mode), operating voltage 15.5 ... 26 V
	
		Ripple 20 mV rms
	
		Transfer characteristics
	
		Deviation at 20 °C (68 °F)
	
		≤ ± 0.1 % incl. non-linearity and hysteresis (source mode 4 ... 20 mA)
	
		≤ ± 0.2 % incl. non-linearity and hysteresis (sink mode 4 ... 20 mA)
	
		≤ ± 0.2 % incl. non-linearity and hysteresis (source mode 1 ... 5 V)
	
		Influence of ambient temperature < 2 µA/K (0 ... 60 °C (32 ... 140 °F)); < 4 µA/K (-20 ... 0 °C (-4 ... 32 °F)) (source mode and sink mode 4 ... 20
	
		mA)
	
		< 0.5 mV/K (0 ... 60 °C (32 ... 140 °F)); < 1 mV/K (-20 ... 0 °C (-4 ... 32 °F)) (source mode 1 ... 5 V)
	
		Frequency range field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
	
		control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
	
		Settling time ≤ 200 ms
	
		Rise time/fall time ≤ 20 ms
	
		Galvanic isolation
	
		Input/Output reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
	
		Input/power supply reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
	
		Output/power supply reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
	
		Indicators/settings
	
		Display elements LED
	
		Control elements DIP-switch
	
		Configuration via DIP switches
	
		Labeling space for labeling at the front
	
		Directive conformity
	
		Electromagnetic compatibility
	
		Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
	
		Conformity
	
		Electromagnetic compatibility NE 21:2006
	
		Degree of protection IEC 60529:2001
	
		Ambient conditions
	
		Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
	
		Mechanical specifications
	
		Degree of protection IP20
	
		Connection screw terminals
	
		Mass approx. 100 g
	
		Dimensions 12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 inch) , housing type A2
	
		Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
	
		Data for application in connection
	
		with hazardous areas
	
		EU-Type Examination Certificate CESI 06 ATEX 021
	
		Marking ¬ II (1)G [Ex ia Ga] IIC , ¬ II (1)D [Ex ia Da] IIIC , ¬ I (M1) [Ex ia Ma] I
	
		Input [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] 
	KCD2-STC-Ex1    
	KCD2-STC-Ex1.ES
	KFD2-CRG2-Ex1.D
	KFD2-HLC-Ex1.D
	KFD2-HLC-Ex1.D.2W
	KFD2-STC4-Ex1
	KFD2-STC4-Ex1.2O
	KFD2-STC4-Ex1.2O.H
	KFD2-STC4-Ex1.H
	KFD2-STC4-Ex2
	KFU8-CRG2-Ex1.D
	KCD2-STC-Ex1.2O
	KCD2-STC-Ex1.2O.ES
	KCD2-STC-Ex1.ES.SP
	KCD2-STC-Ex1.SP
	KFD2-STC3-Ex1
	KFD2-STC4-Ex1-Y1
	KFD2-STC4-Ex1.2O-Y1
	KFD2-STC4-Ex1.ES
	KFD2-STC4-Ex2-Y1
	KFD2-STC5-Ex1
	KFD2-STC5-Ex1.2O
	KFD2-STC5-Ex1.2O.H
	KFD2-STC5-Ex1.H
	KFD2-STC5-Ex2
	KFD2-STC5-Ex2
	KFD2-STC5-Ex2
	KFD2-STV4-Ex1.2O-1
	KFD2-STV4-Ex2-1
	KFD2-STV4-Ex2-2
	KFD2-STV5-Ex1-1
	KCD2-STC-Ex1.2O.DE
	KFD2-HLC-Ex1.D.4S
	KFD2-STV4-Ex1.2O-2
	KCD2-STC-Ex1.HC
	KCD2-STC-Ex1.HC.SP
	KFD2-STC4-Ex1
	KFD2-STC4-Ex1-Y1
	KFD2-STC4-Ex1.2O
	KFD2-STC4-Ex1.2O-Y1
	KFD2-STC4-Ex1.2O.H
	KFD2-STC4-Ex1.H
	KFD2-STV4-Ex1-1
	KFD2-STV4-Ex1-2
	KFD2-STV4-Ex1.2O-1
	KFD2-STV4-Ex2-1
	KFD2-STV4-Ex2-2
	KFD2-STV4-Ex1.2O-2
	KFD2-STC3-Ex1
	KCD2-STC-Ex1-Y1
		-----------------------------------
	
		Lily
	
		HONGKONG XIEYUAN TECH CO., LIMITED
	
		T: 86-027-85581877 F: 86-027-85309780 
	
		Mail:lily@whxyauto.com 
	
		Ad: 7-A16,Caishen Commercial Plaza,Hankou Railway Station,Wuhan, Hubei, China
	
		Web: www.hkxytech.com
	 
			 
		 
	 
							